Series Peerless Pinnacle Oil |
| Model Number1 |
Input2 |
Heating Capacity3, MBH |
Net I=B=R Ratings Water4, MBH |
AFUE5, % |
| GPH |
MBH |
| PO-70 |
0.50 |
70 |
64 |
56 |
91.7 |
| PO-70A1 |
0.50 |
70 |
65 |
56 |
92.0 |
| PO-84 |
0.60 |
84 |
77 |
67 |
91.3 |
| PO-84A1 |
0.60 |
84 |
77 |
67 |
91.8 |
1 Models PO-70A and PO-84A designate boilers using an alternate minimum vent length of 25 equivalent feet.
2 Firing Rate is based on commercial standard #2 fuel oil with a heating value of 140,000 Btu/gallon. Burner input is based on a maximum altitude of 2,000 ft - for higher altitudes consult the factory.
3 Heating Capacity ratings are based on U.S. Government standard tests, with 13.0% CO².
4 the Net I=B=R Output Ratings are based on a pick-up allowance of 1.15. Consult the factory before selecting a boiler for gravity hot water installations or installations having unusual piping and pick-up requirements, such as intermittent system operation and extensive piping systems.
5 Heating Capacity, Net I=B=R Output, and Annual Fuel Usage Efficiency (AFUE) are based on testing required by the FTC and are 3rd Party Verified.
Don't see the information you need? See the "Related Documents" tab for product resource downloads.